Annex & Granny Flat Cable Sizing Calculator

Calculate the correct submain cable size for annexes, granny flats, and self-contained accommodation

Annex Cable Quick Facts

  • Typical annex submain: 63A-100A depending on facilities
  • SWA cable required for buried runs between buildings
  • Annex needs its own consumer unit with RCD protection
  • Consider electric heating, cooking, and future EV charging
  • Part P notification required for new consumer unit installation

Cable Size Calculator

BS 7671:2018+A2:2022 compliant

Need a Qualified Electrician?

Get quotes from vetted, local contractors for your annex installation

Get Free Quotes

Common Annex Installations

1

Basic annex (lighting, sockets, small appliances)

63A submain, 16mm² SWA for runs up to 25m

2

Annex with electric shower + cooking

63A-80A submain, 25mm² SWA for typical runs

3

Full annex with electric heating

80A-100A submain, 25mm² or 35mm² SWA

4

Annex above garage (short run)

63A submain, may use smaller cable for very short runs

5

Annex with future EV charger provision

Size for additional 32A - consider 100A submain minimum

Related Outbuilding & Submain Calculations

Annexes share similar requirements with garden offices and garage workshops. If your annex includes electric heating, see our storage heater guide. Planning EV charging? Check our EV charger calculator to factor into your submain sizing.

Annex Submain Cable Sizing

A submain cable supplies a distribution board (consumer unit) in a separate building from the main supply. For annexes, this means running SWA cable from the house consumer unit to a new consumer unit in the annex. The submain must be sized for the maximum demand of all circuits in the annex, with allowance for diversity and future additions.

Annex Electrical Installation Costs (2024)

Typical UK installation costs including submain, consumer unit, and circuits.

Installation ScenarioMaterialsLabourTotal
Basic annex submain (<15m)£400-700£500-800£900-1500
Standard annex submain (15-25m)£600-1000£600-900£1200-1900
Long run annex submain (25m+)£800-1400£700-1100£1500-2500
Annex consumer unit (6-10 way)£200-400£300-500£500-900
Complete annex electrical fit-out£1500-3000£2000-4000£3500-7000

Prices as of 2024. Costs vary by annex size, cable run, and specification.

Maximum Demand Calculation

Maximum demand estimates the peak electrical load an annex will draw simultaneously. It accounts for diversity - not all appliances run at once. Typical annex calculation: 100% of largest load (usually shower or heating) + 40% of remaining loads. A well-equipped annex might have 15-20kW connected load but 8-12kW maximum demand.

Diversity in Annex Calculations

Diversity recognises that not all annex appliances run simultaneously at full load. BS 7671 and IET guidance provide diversity allowances: 100% for largest appliance, reducing percentages for others. Without diversity, a typical annex might calculate at 40kW+ but actual maximum demand is usually 15-25kW.

PME Earthing Considerations

Properties with PME (Protective Multiple Earthing) have specific requirements for supplies to outbuildings. If the submain exceeds certain lengths or the annex has extraneous metalwork, additional earth electrodes may be required. Your electrician must assess PME implications for annex installations.

Frequently Asked Questions

Get Quotes from Local Electricians

Looking for a qualified electrician for your annex installation? Tell us about your project and we'll connect you with vetted contractors in your area. Free, no obligation quotes.

Trade professional or electrical business? Use the form above and let us know - we offer lead referrals in your area, bulk calculation tools, and white-label partnerships for merchants and suppliers.

More Electrical Calculators

Voltage drop, conduit fill, earth fault loop impedance and more. All BS 7671 compliant, all free.

View All Calculators