Shed & Summer House Cable Sizing Calculator
Calculate the correct cable size for sheds, summer houses, and garden building power supplies
Shed & Summer House Cable Quick Facts
- Most sheds need 16A-32A supply depending on use
- SWA cable required for buried outdoor runs
- RCD protection mandatory for outdoor circuits
- Minimum burial depth: 450mm (600mm under driveways)
- Outdoor isolator switch recommended at shed entry
Cable Size Calculator
BS 7671:2018+A2:2022 compliant
Need a Qualified Electrician?
Get quotes from vetted, local contractors for your shed installation
Common Shed & Summer House Installations
Basic shed (lighting + sockets only)
16A circuit, 2.5mm² SWA for runs up to 30m
Summer house with heating
20A-32A circuit, 4mm² or 6mm² SWA depending on length
Shed with power tools
32A circuit recommended, 6mm² SWA for most runs
Summer house with kitchen appliances
32A circuit, 6mm² SWA, consider dedicated circuits
Long run to bottom of garden (40m+)
Upsize cable for voltage drop - likely 6mm² or 10mm²
Related Garden & Outbuilding Calculators
For larger garden buildings, see our garden office calculator with submain guidance. Planning workshop use? Check the garage and workshop guide. Add outdoor lighting to illuminate the path to your shed.
Shed & Summer House Cable Sizing
Garden building cable sizing determines the conductor size needed to safely supply power to sheds and summer houses. Unlike indoor circuits, outdoor runs require SWA (Steel Wire Armoured) cable for mechanical protection when buried. Cable must handle the expected load while keeping voltage drop acceptable over the outdoor distance.
Shed Electrical Installation Costs (2024)
Typical UK installation costs including SWA cable, groundwork, and labour.
| Installation Scenario | Materials | Labour | Total |
|---|---|---|---|
| Basic shed supply (<15m) | £150-280 | £200-350 | £350-630 |
| Standard shed supply (15-25m) | £250-400 | £280-420 | £530-820 |
| Summer house with consumer unit | £350-550 | £400-600 | £750-1150 |
| Long run supply (30m+) | £400-700 | £450-650 | £850-1350 |
| Outdoor isolator switch | £40-80 | £60-100 | £100-180 |
Prices as of 2024. Costs vary by cable run length and ground conditions.
SWA Cable for Garden Buildings
Steel Wire Armoured (SWA) cable is the standard choice for buried outdoor runs to sheds and summer houses. The steel armour provides mechanical protection against accidental damage from garden tools. SWA can be direct buried at minimum 450mm depth with sand surround and warning tape, or run through ducting.
Voltage Drop for Garden Runs
Long cable runs to sheds cause voltage drop - power tools may run slowly, lights dim. BS 7671 allows 5% drop maximum (11.5V on 230V). At 16A, 2.5mm² cable drops about 18mV per metre. A 30m run at 16A drops 8.6V (3.7%) - acceptable. Our calculator checks this automatically.
Outdoor Circuit Protection
Garden circuits face unique hazards: moisture, wildlife damage, garden tool strikes. Protection includes: RCD for earth faults, MCB for overload, SWA for mechanical protection, IP-rated enclosures for connections. All outdoor electrical equipment must be suitable for the conditions.
Frequently Asked Questions
Related Electrical Calculators
Get Quotes from Local Electricians
Looking for a qualified electrician for your shed installation? Tell us about your project and we'll connect you with vetted contractors in your area. Free, no obligation quotes.
Trade professional or electrical business? Use the form above and let us know - we offer lead referrals in your area, bulk calculation tools, and white-label partnerships for merchants and suppliers.
More Electrical Calculators
Voltage drop, conduit fill, earth fault loop impedance and more. All BS 7671 compliant, all free.
View All Calculators